Alarm information:
Cause |
Detected, on switch on, a difference between the quota stored at power-off and the quota read by the transducer greater than max_d_raw |
<axis> |
Axis number (1-32) |
Output condition |
Retentive quota management enabled |
Effect |
Energization is removed from the power set and the Axis Bit in the c0_done variable is reset to zero (if power management provides for this) |
What to do |
Recalibrate the axis by performing the homing procedure |
Alarm mask |
am[<axis>].0 |
Alarm par prominent |
No |
Alarm type |
|
Notes |
It is possible to avoid resetting the corresponding bit in variable c0_done by bit 20 of variable sys_cfg |