Alarm information:
Cause |
Problems on FIELDBUS network |
<id> |
WS Robox number. |
<code> |
Error codes: •0x000000 = No Communication in operational •0x000001 = Missing Rx PDO 1 for the nr. of sampling specified in CAN node diagnostic (see CANopen Configuration Editor) •0x000002 = Missing Rx PDO 2 for the nr. of sampling specified in the CAN node diagnostic (see CANopen Configuration Editor) •0x000004 = Missing Rx PDO 3 for the nr. of sampling specified in the CAN node diagnostic (see CANopen Configuration Editor) •0x000008 = Missing Rx PDO 4 for the nr. of sampling specified in the CAN node diagnostic (see CANopen Configuration Editor) •0x000010 = Before time Rx PDO 1 •0x000020 = Before time Rx PDO 2 •0x000040 = Before time Rx PDO 3 •0x000080 = Before time Rx PDO 4 •0x00000100 = Missing mandatory Ws •0x00000200 = Missing Ws •0x00000400 = Last Request RTR failed •0x00000800 = Ws Presence imposed •0x00001000 = Reconfiguring Ws •0x00002000 = Error during reconfiguration •0x00004000 = •0x00008000 = •0x00010000 = Emergency Message present •0x00020000 = No communication (in operational mode) •0x00040000 = Ws Kind : Mandatory •0x00080000 = Ws kind : Reloadable on connection •0x00100000 = Configuration satisfactory done •0x00200000 = Ws not connected on first configuration •0x00400000 = Problem occours during configuration on SDO command •0x00800000 = Problem occours during configuration on NMT command •0x010000 = Configuration done •0x02000000 = •0x04000000 = •0x08000000 = •0x10000000 = •0x20000000 = •0x40000000 = Ws not started •0x80000000 = Undefined Ws |
Output condition |
RTE diagnosed one of the malfunctions listed above |
Effect |
Communication does not work |
What to do |
Verify: •Programming of PDOs and communication data •Wiring |
Alarm mask |
am[33].3 |
Alarm par prominent |
Yes |
Alarm type |
|
Notes |
Before RTE v33.21.12 the alarm name was "80 can ws <id> fault <code>" |