Please enable JavaScript to view this site.

Axioline Smart Elements, temperature recording module, analog RTD inputs: 4 (Pt 100), connection method: 3-wire, degree of protection: IP20

Note: Only some information in the module data sheet is given below. Please refer to the data sheet itself for more details.

Connections

connessione_axl_se_rtd4_pt100

Input/Output Word

Four INPUT WORDs and four OUTPUT WORDs are allocated to the module:

Each INP_W corresponds to one pt100 input.

The four OUT_W are not used.

Representation of measured values

Input data (hex)

Input data (dec)

Temperature

0x8001

overrange

> upper limit

0x2134

8500

+850.0 (upper limit)

0x03E8

1000

+100.0

0x0001

1

+0.1

0x0000

0

0

0xFFFF

-1

-0.1

0xF830

-2000

-200.0 (lower limit)

0x8080

underrange

< lower limit

 

  