Alarm information:

Cause

Unable to make operative the PROF. INT board.

Possible misconfiguration

<code>

Error code:

8 = Configuration (number of 32-byte blocks) received from DP master different from that set in pfb.cfg file

9 = Profibus communication management hardware error (SPC3)

Output condition

 

Effect

Profibus management disabled

What to do

With version of RTE less than or equal to v34.27.01. turn the control off and on again to try to reactivate communication.

With version of RDE greater than or equal to v34.27.02 is reset if the cause does not persist

Alarm mask

am[33].5

Alarm par prominent

No

Alarm type

Autodia

Notes

You can disable it and generate warning 9247 by setting to 1 sys_flag_2.10

 

  