Alarm information:
Cause |
The cause varies according to the value of <code>: •the drive is in "operation enabled" and the sync message (SM mode or DC mode) does not arrive after 1.3 periods of the "communication cycle period," and is therefore considered as "missing Sync message" •no data is received from the CU, or the CU does not read the data correctly •no data exchange with Sinamics. Possible causes: othe EtherCAT watchdog has expired while the ESM is in Op mode othe maximum variation of the Sync PLL is more than 10% of the Sync base time othe error of the Sync PLL is beyond an acceptable value oCurrent Sync mode is in FreeFun |
<axis> |
Axis number (1-32) |
<code> |
Error code (1, 2 or 3) |
Output condition |
|
Effect |
Power set power drop |
What to do |
Check network |
Alarm mask |
am[34].10 |
Alarm par prominent |
Yes |
Alarm type |
|
Notes |
Introduced in RTE v34.18.2. Alarm related to Sinamics drives connected on EtherCAT bus. Refer to the REB board manual for more information. Performance is enabled by indicating in RTE design configuration (axes, transducer/actuator) the Sinamics family drives |