Please enable JavaScript to view this site.

Function for reading INPUT REGISTER on modbus server by specifying unit ID.

Syntax

i32 mbcu_read_inp_reg (i32 mbc, i32 unitID, i32 offsIRStart, i32 nIR, i32 endian, dest)

mbc

Handle value returned by mbc_init()

unitID

Value of the unit ID to be used

offsIRStart

Initial index of the INPUT REGISTER

nIR

Number of INPUT REGISTER to be read

endian

Type of endian to be used:

Value

Meaning

0 [EM_B_16]

Big Endian in the single word. (default)

1 [EM_L_16]

Little Endian in the single word

2 [EM_B_32]

Big Endian in 32 bits

3 [EM_L_32]

Little Endian in 32 bits

4 [EM_MB_32]

Middle Big Endian in 32 bits

5 [EM_ML_32]

Middle little Endian in 32 bits

6 [EM_B_64]

Big Endian in 64 bits

7 [EM_L_64]

Little Endian in 64 bits

8 [EM_MB_64]

Middle Big Endian in 64 bits

9 [EM_ML_64]

Middle little Endian in 64 bits

dest

Area where to put read data.

Can be i16/u16/i32/float/real or array of i16/u16/i32/float/real

Result

Returns:

Value

Meaning

0 [MBC_OK]

Command executed

-1 [MBC_INVAL]

Invalid arguments

-2 [MBC_BUSY]

Resource occupied

-3 [MBC_PERM]

Permission denied

-4 [MBC_CONN]

Connection failed

-5 [MBC_NOBUFS]

Buffer exhausted

-6 [MBC_NOMEM]

Insufficient memory

-7 [MBC_TX_ERR]

Transmission error

-8 [MBC_RX_ERR]

Receive error

-9 [MBC_TIMEOUT]

Blocking command timeout

-10 [MBC_EXC_CODE_1]

Response with exception 1 (function code not supported by server)

-11 [MBC_EXC_CODE_2]

Response with exception 2 (invalid address)

-12 [MBC_EXC_CODE_3]

Response with exception 3 (invalid quantity or value)

-13 [MBC_EXC_CODE_4]

Response with exception 4 (operation failed)

-14 [MBC_WRONG_ANSWER]

Invalid response

-15 [MBC_INVAL_MBC]

Invalid mbc id

Validity

Task

Note

The function is blocking. Exits only when the task is completed

 

  

Keyboard Navigation

F7 for caret browsing
Hold ALT and press letter

This Info: ALT+q
Page Header: ALT+h
Topic Header: ALT+t
Topic Body: ALT+b
Contents: ALT+c
Search: ALT+s
Exit Menu/Up: ESC